TECHNICAL INFORMATION

 

Wire Tightening

The Terminal Block clamping parts when tightened within the torque range ensure optimum performance as given below :

  •  The voltage drop (contact resistance) is well below specified limits

  •  The wire gets clamped perfectly to form gas tight connection

  •  The clamping yoke does not get damaged mechanically The tightening torque

according to IEC 60947-7-1 table 4, is safe limit of torque  which guarantees successful clamping of the connected wire. 

Connectwell Terminal Blocks tightening torque data is given in respective Product pages.

All Connectwell Terminal Blocks are designed to function with rated wire size as per respective AWG (American Wire Gauge) or Metric size/system.

The terminal blocks are tested for Gauge Insertion test (as per VDE 0660) 

 Tightening Toreque for Screw Clamp Terminal Blocks

Terminal Blocks Thread Size of Fastener Recommended Torque Value

CTS2.5UN/CPT(M)/CPT5

M 2.5 0.4 Nm

CTS2.5(M)/CMST1/CMST2

M 2.6 0.4 Nm

CTS2.5/CMT4/CMB4/CDL4U/ODL4U/
CGT4U/CTS4UN/CTS4SC/CSTSB3/
CSFL4U/CSDL4U/CKT4U/CPT7.5/DDFL4U/
DDFL4U(E)/DDFL4U(E)LR/CMC1-2/CMC2-2

M 3 0.5 Nm

CTS6/CTS6SC/CTS6U/CSFL6U/CENC4

M 3.5 0.8 Nm

CTS10/10U/CTS16/16U/CSTSN4/B4/CDTTS/
CTS10SC/CGT10U/DDPT/CDTTU/CSTSN4U

M 4 1.2 Nm

CTS25U/CSTSB5/N5/N5(15)/RN5/N5U/CENC16

M 5 2.0 Nm

CTS35/CTS35U/CENC35/CGT35U

M 6.0 2.0 Nm

CTS35L/35LS/CSTSRN6/CSTSN6

M 6.0 2.8 Nm

CTS70L/70LS/CTS95L/95LS

M 10.0 10.0 Nm
     

Representative Picture of Gauge Type A and Type B